Decaying DC (DDC) current due to impact loads causes detrimental consequences in weak grids. In this paper, the active power filter (APF) is enhanced to simultaneously compensate for the undesired harmonics, negative sequence components and the DDC component in the event of a transient. To this end, first, a novel DDC component detection method is mathematically deduced for single-phase transient current, followed by its extension to the three-phase system. With respect to existing techniques, the proposed method has a significantly reduced detection time from 1 grid cycle to approximately 0.5 grid cycle. By further exploiting the transient signal properties in dq-frame, the three-phase fundamental-frequency current in positive sequence can be separated. Finally, the enhanced APF control scheme is developed based on the proposed detection algorithm. Experiments verified the effectiveness and advancement of the proposed technique.

Decaying DC and Harmonic Components Detection for Absorbing Impact Load Currents in Weak Grids

Liu X.;
2021-01-01

Abstract

Decaying DC (DDC) current due to impact loads causes detrimental consequences in weak grids. In this paper, the active power filter (APF) is enhanced to simultaneously compensate for the undesired harmonics, negative sequence components and the DDC component in the event of a transient. To this end, first, a novel DDC component detection method is mathematically deduced for single-phase transient current, followed by its extension to the three-phase system. With respect to existing techniques, the proposed method has a significantly reduced detection time from 1 grid cycle to approximately 0.5 grid cycle. By further exploiting the transient signal properties in dq-frame, the three-phase fundamental-frequency current in positive sequence can be separated. Finally, the enhanced APF control scheme is developed based on the proposed detection algorithm. Experiments verified the effectiveness and advancement of the proposed technique.
2021
ELETTRICI
File in questo prodotto:
File Dimensione Formato  
Decaying_DC_and_Harmonic_Components_Detection_for_Absorbing_Impact_Load_Currents_in_Weak_Grids.pdf

Accesso riservato

Descrizione: Articolo principale
: Publisher’s version
Dimensione 791.38 kB
Formato Adobe PDF
791.38 kB Adobe PDF   Visualizza/Apri
TPD_DDC_author_ver.pdf

accesso aperto

Descrizione: Articolo principale
: Pre-Print (o Pre-Refereeing)
Dimensione 884.77 kB
Formato Adobe PDF
884.77 kB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1180668
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 20
  • ???jsp.display-item.citation.isi??? 15
social impact