This paper proposes a novel estimation scheme for angular quantities extraction under disturbed network conditions; a robust identification of the network angular frequency and of its derivative are crucial for the synthetic inertia provision from grid-connected converters. The newly proposed architecture is derived from the Second Order / Second Order Generalized Integrator scheme (SO-SOGI), an algorithm exploited to extract the fundamental harmonic component from phase voltages measurements, with the introduction of an additional decoupling feedback for negative sequence compensation. The effectiveness and robustness of the proposed technique are compared, both analytically and experimentally, with other schemes already available in literature.
Experimental validation of a novel angular estimator for synthetic inertia support under disturbed network conditions
Bolzoni, Alberto;Perini, Roberto
2019-01-01
Abstract
This paper proposes a novel estimation scheme for angular quantities extraction under disturbed network conditions; a robust identification of the network angular frequency and of its derivative are crucial for the synthetic inertia provision from grid-connected converters. The newly proposed architecture is derived from the Second Order / Second Order Generalized Integrator scheme (SO-SOGI), an algorithm exploited to extract the fundamental harmonic component from phase voltages measurements, with the introduction of an additional decoupling feedback for negative sequence compensation. The effectiveness and robustness of the proposed technique are compared, both analytically and experimentally, with other schemes already available in literature.File | Dimensione | Formato | |
---|---|---|---|
final_epe_10.pdf
accesso aperto
Descrizione: Articolo principale
:
Pre-Print (o Pre-Refereeing)
Dimensione
494.68 kB
Formato
Adobe PDF
|
494.68 kB | Adobe PDF | Visualizza/Apri |
I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.