The present paper investigates the conditions which make possible the occurrence of delayed current zeros in power stations equipped with three-winding step-up transformers. The current resulting from a fault at the LV-terminals of the three-winding step-up transformer is usually characterized by a high degree of asymmetry and can lead to delayed zeros. Despite the delayed current zeros resulting from this type of fault are not considered in IEEE Standard C37.013-1997 (R2008) and in its amendment IEEE Standard C37.013a-2007, they should be taken into account when studying the suitability of a generator circuit-breaker for the application. The conditions which make possible the occurrence of such a phenomenon are analysed by means of Laplace transform. The corresponding results in time-domain are validated by comparing the waveform of the current obtained with ATP simulations.

Application of Laplace Transform to Analyse Delayed Current Zeros in Power Stations Which Employ Three-Winding Step-Up Transformer

DELFANTI, MAURIZIO;PALAZZO, MIRKO
2013-01-01

Abstract

The present paper investigates the conditions which make possible the occurrence of delayed current zeros in power stations equipped with three-winding step-up transformers. The current resulting from a fault at the LV-terminals of the three-winding step-up transformer is usually characterized by a high degree of asymmetry and can lead to delayed zeros. Despite the delayed current zeros resulting from this type of fault are not considered in IEEE Standard C37.013-1997 (R2008) and in its amendment IEEE Standard C37.013a-2007, they should be taken into account when studying the suitability of a generator circuit-breaker for the application. The conditions which make possible the occurrence of such a phenomenon are analysed by means of Laplace transform. The corresponding results in time-domain are validated by comparing the waveform of the current obtained with ATP simulations.
2013
EuroCon 2013
978-146732232-4
Delayed current zeros, Fault currents, Generator circuit-breaker, Laplace transform, Three-winding step-up transformer
File in questo prodotto:
File Dimensione Formato  
06625182.pdf

Accesso riservato

: Post-Print (DRAFT o Author’s Accepted Manuscript-AAM)
Dimensione 1.74 MB
Formato Adobe PDF
1.74 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/741366
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 3
  • ???jsp.display-item.citation.isi??? ND
social impact