The paper proposes a detailed model of the thermal and mechanical part of a microturbine; in fact this model accounts for three control loops: a speed controller (for primary frequency control), an acceleration control loop, which limits the rotor acceleration in case of sudden loss of load or in case of start-up, and a controller which limits the temperature of the exhaust gases below the maximum admissible temperature. Moreover the paper adopts a PV (active power – voltage) control of the inverter for the microturbine operation on the grid; the usual scheme adopted is a PQ (active power – reactive power) control, which regulates the values of active and reactive powers injected by the inverter into the grid. The use of a PV control scheme allows to evaluate the contribution of microturbines to voltage support in distribution grids. In case of isolated operation a Vf (voltage – frequency) scheme is adopted. A test grid is implemented and the results of the simulations are described and discussed.

A Microturbine Model including its Control for the investigation of the effects of Distributed Generation in distribution networks

GRILLO, SAMUELE;
2007-01-01

Abstract

The paper proposes a detailed model of the thermal and mechanical part of a microturbine; in fact this model accounts for three control loops: a speed controller (for primary frequency control), an acceleration control loop, which limits the rotor acceleration in case of sudden loss of load or in case of start-up, and a controller which limits the temperature of the exhaust gases below the maximum admissible temperature. Moreover the paper adopts a PV (active power – voltage) control of the inverter for the microturbine operation on the grid; the usual scheme adopted is a PQ (active power – reactive power) control, which regulates the values of active and reactive powers injected by the inverter into the grid. The use of a PV control scheme allows to evaluate the contribution of microturbines to voltage support in distribution grids. In case of isolated operation a Vf (voltage – frequency) scheme is adopted. A test grid is implemented and the results of the simulations are described and discussed.
File in questo prodotto:
File Dimensione Formato  
Bucarest 2007.pdf

Accesso riservato

: Post-Print (DRAFT o Author’s Accepted Manuscript-AAM)
Dimensione 333.87 kB
Formato Adobe PDF
333.87 kB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/575398
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact