Preserving high-value historic buildings requires a careful balance between occupant thermal comfort, conservation of sensitive materials and overall energy efficiency. In such regards, the study presents a comprehensive thermohygrometric assessment of the Church of San Giacomo in Como, integrating longterm microclimatic monitoring and dynamic state energy modelling to support the definition of conservation and compatible HVAC strategies. A whole-building dynamic simulation model was developed in EnergyPlus to evaluate multiple heating scenarios focused on a low-temperature radiant floor system integrated beneath the existing stone pavement. The comparative analysis of different setpoints (14 °C, 16 °C, 18 °C) demonstrates that continuous operation at 16 °C provides the most favourable balance between indoor stability, energy performance and material conservation risk, mitigating both high humidity in wintertime and excessive dryness associated with higher setpoints. Beyond informing HVAC design choices, the multilevel methodological framework adopted offers a quantitative basis for defining visitor flow management strategies. By characterising the microclimatic sensitivity of the indoor environment to visitor perturbations, the approach enables the formulation of occupancy schedules based on proven data aimed at maintaining the indoor climate within optimal conservation conditions.

Microclimate Control Strategies for the Protection of Historic Buildings: The Case of the Church of San Giacomo in Como

Huerto-Cardenas, Harold Enrique;Leonforte, Fabrizio;Aste, Niccolo;Del Pero, Claudio;Vecchierelli, Federica
2026-01-01

Abstract

Preserving high-value historic buildings requires a careful balance between occupant thermal comfort, conservation of sensitive materials and overall energy efficiency. In such regards, the study presents a comprehensive thermohygrometric assessment of the Church of San Giacomo in Como, integrating longterm microclimatic monitoring and dynamic state energy modelling to support the definition of conservation and compatible HVAC strategies. A whole-building dynamic simulation model was developed in EnergyPlus to evaluate multiple heating scenarios focused on a low-temperature radiant floor system integrated beneath the existing stone pavement. The comparative analysis of different setpoints (14 °C, 16 °C, 18 °C) demonstrates that continuous operation at 16 °C provides the most favourable balance between indoor stability, energy performance and material conservation risk, mitigating both high humidity in wintertime and excessive dryness associated with higher setpoints. Beyond informing HVAC design choices, the multilevel methodological framework adopted offers a quantitative basis for defining visitor flow management strategies. By characterising the microclimatic sensitivity of the indoor environment to visitor perturbations, the approach enables the formulation of occupancy schedules based on proven data aimed at maintaining the indoor climate within optimal conservation conditions.
2026
Resilience, Multi-risk Assessment and Monitoring
9783032398666
9783032398673
Historic Buildings, Preventive Conservation, Visitors Flux Management, Microclimate Monitoring, Adaptive Control Strategies, Building Energy Simulation
File in questo prodotto:
File Dimensione Formato  
2026-Microclimate Control Strategies for the Protection of Historic Buildings. The Case of the Church of San Giacomo in Como.pdf

Accesso riservato

: Publisher’s version
Dimensione 784.94 kB
Formato Adobe PDF
784.94 kB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1330206
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
  • OpenAlex ND
social impact