Following the COVID-19 pandemic, considerable attention is now being paid to building ventilation as a key measure to control the transmission of respiratory diseases and promote well-being among the occupants. This is espe-cially critical in high turnover environments of public buildings, such as waiting rooms, where ensuring adequate Indoor Air Quality (IAQ) through mechanical ventilation (MV) systems is essential, as the daily constant exchange of individuals can facilitate cross-infections. This work presents a comprehensive investigation of long-term air monitoring conducted in a waiting room in Milan, Italy, equipped with a conventional MV system featuring schedule-based activation. Environmen-tal parameters such as air temperature, relative humidity, CO2, and other common indoor pollutants were recorded, along with the turnover of individuals. Anal-yses showed that the installed MV system can provide suitable IAQ levels and limited infection risk during the considered periods. Additionally, a CO2-based control strategy was proposed to balance IAQ and energy consumption in these kinds of environments, revealing 50% potential energy savings compared to the schedule-based control without compromising IAQ levels.

A Comprehensive Investigation of Long-Term Air Monitoring in a Waiting Room Equipped with a Mechanical Ventilation System

R. Cardelli;M. Buzzetti;M. Gola;F. Zagarella;S. Ferrari
2026-01-01

Abstract

Following the COVID-19 pandemic, considerable attention is now being paid to building ventilation as a key measure to control the transmission of respiratory diseases and promote well-being among the occupants. This is espe-cially critical in high turnover environments of public buildings, such as waiting rooms, where ensuring adequate Indoor Air Quality (IAQ) through mechanical ventilation (MV) systems is essential, as the daily constant exchange of individuals can facilitate cross-infections. This work presents a comprehensive investigation of long-term air monitoring conducted in a waiting room in Milan, Italy, equipped with a conventional MV system featuring schedule-based activation. Environmen-tal parameters such as air temperature, relative humidity, CO2, and other common indoor pollutants were recorded, along with the turnover of individuals. Anal-yses showed that the installed MV system can provide suitable IAQ levels and limited infection risk during the considered periods. Additionally, a CO2-based control strategy was proposed to balance IAQ and energy consumption in these kinds of environments, revealing 50% potential energy savings compared to the schedule-based control without compromising IAQ levels.
2026
Proceedings of the 15th REHVA HVAC World Congress - CLIMA 2025
9783032068095
9783032068101
Air monitoring, Mechanical Ventilation, Waiting room, Infection risk, Occupancy pattern
File in questo prodotto:
File Dimensione Formato  
978-3-032-06810-1_21.pdf

Accesso riservato

: Publisher’s version
Dimensione 1.59 MB
Formato Adobe PDF
1.59 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1311460
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus ND
  • ???jsp.display-item.citation.isi??? ND
social impact