Crosstalk coupling effects may cause performance degradation to low-power instrument transformers (LPITs). In this article, the measurement method and then the crosstalk mechanism for a novel low-voltage combined low-power current and voltage instrument transformer are presented. Subsequently, the crosstalk characterization by means of measurement test is comprehensively performed with respect to IEC 61869 Standards. More specifically, the impact of an adjacent grounded metallic wall is evaluated, and then, the immunity behavior against external electric and magnetic fields related to the proximity of an energized and a current carrying conductor is verified. An integration test is further conducted on the combined transformer to validate proper operation and underlying mutual coupling between the voltage and current sensors. Suggestions are provided for the purpose of improving the measuring accuracy of the combined transformer.

Crosstalk Estimation for a Novel Low-Voltage Combined Low-Power Instrument Transformer

Huangfu Y.;Faifer M.;Ottoboni R.;Toscani S.
2025-01-01

Abstract

Crosstalk coupling effects may cause performance degradation to low-power instrument transformers (LPITs). In this article, the measurement method and then the crosstalk mechanism for a novel low-voltage combined low-power current and voltage instrument transformer are presented. Subsequently, the crosstalk characterization by means of measurement test is comprehensively performed with respect to IEC 61869 Standards. More specifically, the impact of an adjacent grounded metallic wall is evaluated, and then, the immunity behavior against external electric and magnetic fields related to the proximity of an energized and a current carrying conductor is verified. An integration test is further conducted on the combined transformer to validate proper operation and underlying mutual coupling between the voltage and current sensors. Suggestions are provided for the purpose of improving the measuring accuracy of the combined transformer.
2025
Crosstalk
low-power instrument transformer (LPIT)
low-voltage (LV)
Rogowski coil (RC)
smart grids
File in questo prodotto:
File Dimensione Formato  
Crosstalk_Estimation_for_a_Novel_Low-Voltage_Combined_Low-Power_Instrument_Transformer.pdf

accesso aperto

: Publisher’s version
Dimensione 2.03 MB
Formato Adobe PDF
2.03 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1295991
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? 1
social impact