Grid-connected photovoltaic (PV) systems are commonly designed for maximum energy production. However, as their presence grows, revised grid regulations increasingly require these systems to partially adhere to the primary frequency regulation (PFR) by reducing their power production when the grid frequency exceeds the nominal value. Nevertheless, full participation in PFR of PV systems, without battery storage, would require operating with a dedicated active power reserve to be utilized in the event of underfrequency conditions. This paper presents a model-based (MB) flexible power point tracking (FPPT) algorithm for PV systems. Results of a microgrid simulation show that the proposed algorithm enables a PV system with a nominal power of 100 kW to maintain a 20 kW active power reserve under various irradiation and temperature conditions, with a relative error lower than 3%. Furthermore, a simulation of the PV system assisting in primary frequency regulation is presented. Thanks to the proposed strategy, when employing the algorithm, the frequency deviation is reduced both in the event of underfrequency and overfrequency conditions. By enabling operation with a constant active power reserve, as well as a quick adjustment of the produced active power, in the event of frequency imbalance, the proposed MB algorithm is an interesting candidate for achieving complete PFR capabilities of PV systems.

Model-Based Algorithm for Flexible Power Point Tracking for Photovoltaic Participation in Primary Frequency Regulation

Cristaldi L.;Faifer M.;Laurano C.;Petkovski E.;Toscani S.
2024-01-01

Abstract

Grid-connected photovoltaic (PV) systems are commonly designed for maximum energy production. However, as their presence grows, revised grid regulations increasingly require these systems to partially adhere to the primary frequency regulation (PFR) by reducing their power production when the grid frequency exceeds the nominal value. Nevertheless, full participation in PFR of PV systems, without battery storage, would require operating with a dedicated active power reserve to be utilized in the event of underfrequency conditions. This paper presents a model-based (MB) flexible power point tracking (FPPT) algorithm for PV systems. Results of a microgrid simulation show that the proposed algorithm enables a PV system with a nominal power of 100 kW to maintain a 20 kW active power reserve under various irradiation and temperature conditions, with a relative error lower than 3%. Furthermore, a simulation of the PV system assisting in primary frequency regulation is presented. Thanks to the proposed strategy, when employing the algorithm, the frequency deviation is reduced both in the event of underfrequency and overfrequency conditions. By enabling operation with a constant active power reserve, as well as a quick adjustment of the produced active power, in the event of frequency imbalance, the proposed MB algorithm is an interesting candidate for achieving complete PFR capabilities of PV systems.
2024
photovoltaic systems
microgrids
frequency regulations
maximum power point trackers
flexible power point trackers
File in questo prodotto:
File Dimensione Formato  
energies-17-02049-v2.pdf

Accesso riservato

Dimensione 5.16 MB
Formato Adobe PDF
5.16 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1274682
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 1
  • ???jsp.display-item.citation.isi??? ND
social impact