Gas-insulated systems are widely utilized in the electric power sector to transmit and distribute electrical energy. Sulphur-hexafluoride (SF6) has dominated gas insulation in high-voltage insulation technology since the early 60s. It is a greenhouse gas with a protracted lifespan in the atmosphere. This paper proposes an economical and comparatively more environmentally friendly R507 gas alternative to SF6 for medium-voltage applications. R507 has been analyzed experimentally through power frequency breakdown and lightning impulse testing to validate the performance and theoretical concepts. R507 has a very low liquefaction temperature of −46.7°C, but it must still be mixed with buffer gases such as CO2, N2, or dry air to meet the diverse liquefaction temperature applications. Various field utilization factors under AC and lightning impulse voltages are used in the experiments, along with different electrode geometries, including sphere-to-plane and rod-to-plane (i.e., quasi-homogeneous and inhomogeneous electric field distribution). For comparison, identical experiments are conducted with pure SF6. R507 gas was found to be a promising substitute for SF6 gas, with its dielectric strength being approximately 0.95 times that of SF6 gas. A positive synergistic effect is present between R507 and CO2, along with the good self-recoverability property of the gas mixture. The current research study serves as a fundamental resource for characterizing the R507/CO2 gas mixture insulation properties to be utilized in practical applications.

The Insulation Performance of Novel Refrigerant Gas as an Alternative to SF6 For Medium Voltage Switchgear

Ullah, Zahid;
2024-01-01

Abstract

Gas-insulated systems are widely utilized in the electric power sector to transmit and distribute electrical energy. Sulphur-hexafluoride (SF6) has dominated gas insulation in high-voltage insulation technology since the early 60s. It is a greenhouse gas with a protracted lifespan in the atmosphere. This paper proposes an economical and comparatively more environmentally friendly R507 gas alternative to SF6 for medium-voltage applications. R507 has been analyzed experimentally through power frequency breakdown and lightning impulse testing to validate the performance and theoretical concepts. R507 has a very low liquefaction temperature of −46.7°C, but it must still be mixed with buffer gases such as CO2, N2, or dry air to meet the diverse liquefaction temperature applications. Various field utilization factors under AC and lightning impulse voltages are used in the experiments, along with different electrode geometries, including sphere-to-plane and rod-to-plane (i.e., quasi-homogeneous and inhomogeneous electric field distribution). For comparison, identical experiments are conducted with pure SF6. R507 gas was found to be a promising substitute for SF6 gas, with its dielectric strength being approximately 0.95 times that of SF6 gas. A positive synergistic effect is present between R507 and CO2, along with the good self-recoverability property of the gas mixture. The current research study serves as a fundamental resource for characterizing the R507/CO2 gas mixture insulation properties to be utilized in practical applications.
2024
File in questo prodotto:
File Dimensione Formato  
The_Insulation_Performance_of_Novel_Refrigerant_Gas_as_an_Alternative_to_SF_for_Medium_Voltage_Switchgear.pdf

accesso aperto

: Publisher’s version
Dimensione 2.56 MB
Formato Adobe PDF
2.56 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1263898
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 1
social impact