This paper deals with the assessment of the maximal peak of the overvoltage induced in a power-line network due to the field-to-wire coupling from an external electromagnetic disturbance. A worst-case analysis is here combined with the transmission line model to find the terminal overvoltage, induce by radiated electromagnetic disturbances of constrained energy density and bandlimits. The approach was applied to canonic power line network topologies, from statistic viewpoint, it is demonstrated that dominant coupling can be ascribed to the branch containing the most twisted segments. Accordingly, efforts have been devoted to find analytical solution to overvoltage peak upper bound for the coupling-dominant zigzag branch. In this connection, both versatile implicit solution and approximated explicit expressions of the upper bound are formulated, which reveals the relations between the upper bound of zigzag branch and its segments, quantitively interpreting the effect of segment orientations and length. Finally, numerical simulations corroborate the model validity and suggest that the estimations of upper bound are sufficiently accurate for analyzing practical power line network. This proposed approach will be instructive for power system insulation coordination and protection design.

Upper bound of overvoltage peak induced in power line network above lossless ground due to radiated electromagnetic disturbances

Spadacini, Giordano;Pignari, Sergio A.;
2023-01-01

Abstract

This paper deals with the assessment of the maximal peak of the overvoltage induced in a power-line network due to the field-to-wire coupling from an external electromagnetic disturbance. A worst-case analysis is here combined with the transmission line model to find the terminal overvoltage, induce by radiated electromagnetic disturbances of constrained energy density and bandlimits. The approach was applied to canonic power line network topologies, from statistic viewpoint, it is demonstrated that dominant coupling can be ascribed to the branch containing the most twisted segments. Accordingly, efforts have been devoted to find analytical solution to overvoltage peak upper bound for the coupling-dominant zigzag branch. In this connection, both versatile implicit solution and approximated explicit expressions of the upper bound are formulated, which reveals the relations between the upper bound of zigzag branch and its segments, quantitively interpreting the effect of segment orientations and length. Finally, numerical simulations corroborate the model validity and suggest that the estimations of upper bound are sufficiently accurate for analyzing practical power line network. This proposed approach will be instructive for power system insulation coordination and protection design.
2023
Power line network
Worst-case scenario
Overvoltage
Radiated electromagnetic disturbance
Transmission line model
File in questo prodotto:
File Dimensione Formato  
LT+GS+SP+YX.pdf

accesso aperto

Descrizione: articolo
: Publisher’s version
Dimensione 2.05 MB
Formato Adobe PDF
2.05 MB Adobe PDF Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1259414
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 0
  • ???jsp.display-item.citation.isi??? 0
social impact