The aim of this study was to analyze and compare the performance of an 8 kW ejector-based R290 heat pump system for hot water heating applications that operates with two different expansion devices: a throttling valve and a two-phase ejector. The vapor compression system was designed to compare the unit operating in direct expansion and ejector-based working modes under similar operating conditions. The test results were assessed for overall system performance measured by COP and heating capacity and for single-component operation. The ejector mode allowed operation at the same range of ambient temperatures as direct expansion mode with the potential to completely replace the expansion valve. The COP of ejector system was up to 2.6, which was 38% higher than direct expansion when working under similar conditions for an ambient temperature of -12.8 degrees C. Moreover, the COP in direct expansion mode decreased significantly along the decrease of ambient temperature, whereas for the ejector mode this decrease was considerably smaller.

Experimental analysis of the air-to-water ejector-based R290 heat pump system for domestic application

Fingas R.;Besagni G.;
2024-01-01

Abstract

The aim of this study was to analyze and compare the performance of an 8 kW ejector-based R290 heat pump system for hot water heating applications that operates with two different expansion devices: a throttling valve and a two-phase ejector. The vapor compression system was designed to compare the unit operating in direct expansion and ejector-based working modes under similar operating conditions. The test results were assessed for overall system performance measured by COP and heating capacity and for single-component operation. The ejector mode allowed operation at the same range of ambient temperatures as direct expansion mode with the potential to completely replace the expansion valve. The COP of ejector system was up to 2.6, which was 38% higher than direct expansion when working under similar conditions for an ambient temperature of -12.8 degrees C. Moreover, the COP in direct expansion mode decreased significantly along the decrease of ambient temperature, whereas for the ejector mode this decrease was considerably smaller.
2024
Heat pump
R290
Two-phase ejector
Natural refrigeration
Experimental study
File in questo prodotto:
File Dimensione Formato  
1-s2.0-S135943112301829X-main.pdf

Accesso riservato

: Publisher’s version
Dimensione 2.04 MB
Formato Adobe PDF
2.04 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1258365
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 4
  • ???jsp.display-item.citation.isi??? 0
social impact