Overall measurement accuracy of current transformers is expressed by their accuracy class. When considering the fundamental component, it corresponds to ratio and phase error limits that are relaxed at small current values. As far as low-power current transformers, fixed ratio and phase error limits are prescribed at harmonic components. This paper shows, through numerical simulations, that this approach cannot represent the performance of current transformers in the presence of nonlinearity. A general method to model the behavior of harmonic ratio and phase errors is presented, regardless of the operating principle of the current transformer. This suggests an alternative approach to specify accuracy requirements at a given harmonic, which should depend on its relative magnitude with respect to the fundamental.

Investigating and Modeling the Harmonic Measurement Accuracy of Current Transformers

Faifer M.;Laurano C.;Ottoboni R.;Toscani S.
2022-01-01

Abstract

Overall measurement accuracy of current transformers is expressed by their accuracy class. When considering the fundamental component, it corresponds to ratio and phase error limits that are relaxed at small current values. As far as low-power current transformers, fixed ratio and phase error limits are prescribed at harmonic components. This paper shows, through numerical simulations, that this approach cannot represent the performance of current transformers in the presence of nonlinearity. A general method to model the behavior of harmonic ratio and phase errors is presented, regardless of the operating principle of the current transformer. This suggests an alternative approach to specify accuracy requirements at a given harmonic, which should depend on its relative magnitude with respect to the fundamental.
2022
2022 12th IEEE International Workshop on Applied Measurements for Power Systems, AMPS 2022 - Proceedings
978-1-6654-7034-6
ELETTRICI
current measurement
current transformers
instrument transformers
measurement uncertainty
nonlinear systems
power system harmonics
File in questo prodotto:
File Dimensione Formato  
Investigating_and_Modeling_the_Harmonic_Measurement_Accuracy_of_Current_Transformers.pdf

Accesso riservato

: Publisher’s version
Dimensione 4.21 MB
Formato Adobe PDF
4.21 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1228144
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 2
  • ???jsp.display-item.citation.isi??? 0
social impact