Distributed Energy Resource Management System will enable interoperability in communication with all the elements of the electrical grid. Communication protocol such as IEC61850 is already in the substations because of interoperability and performance in maintaining strict real-time transfer of messages in all the communication levels such as process bus, station bus, and the supervisory level. Integration of distributed energy resources, especially grid to vehicle and vehicle to grid technology, increases the substation boundary and its communication network, which is a safety threat, and they can be a vulnerable point to cyber security attacks. In this work, we analyze the impact of the cyberattack on a modified IEEE 13 node test feeder network that operates with Distributed Energy Resource Management System and IEC61850 as a communication protocol. The threat impact is analyzed using a Hardware-in-the-loop test bench with the integration of a physical communication network layer and Intelligent Electronic Devices connected to the circuit breakers. A Man-in-the-middle attack on the power system network, such as spoofing and false data injection in the supervisory communication layer of IEC61850 MMS involved in the Distributed Energy Resource Management System, are executed.

Analysis of Cyber Security Threat of using IEC61850 in Digital Substations involving DERMS

Harshavardhan Palahalli Mallikarjun;Hemmati M.;Gruosso G.
2022-01-01

Abstract

Distributed Energy Resource Management System will enable interoperability in communication with all the elements of the electrical grid. Communication protocol such as IEC61850 is already in the substations because of interoperability and performance in maintaining strict real-time transfer of messages in all the communication levels such as process bus, station bus, and the supervisory level. Integration of distributed energy resources, especially grid to vehicle and vehicle to grid technology, increases the substation boundary and its communication network, which is a safety threat, and they can be a vulnerable point to cyber security attacks. In this work, we analyze the impact of the cyberattack on a modified IEEE 13 node test feeder network that operates with Distributed Energy Resource Management System and IEC61850 as a communication protocol. The threat impact is analyzed using a Hardware-in-the-loop test bench with the integration of a physical communication network layer and Intelligent Electronic Devices connected to the circuit breakers. A Man-in-the-middle attack on the power system network, such as spoofing and false data injection in the supervisory communication layer of IEC61850 MMS involved in the Distributed Energy Resource Management System, are executed.
2022
2022 International Symposium on Power Electronics, Electrical Drives, Automation and Motion, SPEEDAM 2022
978-1-6654-8459-6
Cyber Security
Cyber-physical systems
GOOSE Messages
Hardware-in-the-loop
IEC61850
Intelligent Electronic Devices
MMS Server
Smart grid
File in questo prodotto:
File Dimensione Formato  
Analysis_of_Cyber_Security_Threat_of_using_IEC61850_in_Digital_Substations_involving_DERMS.pdf

Accesso riservato

Descrizione: articolo
: Publisher’s version
Dimensione 1.34 MB
Formato Adobe PDF
1.34 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1225252
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 4
  • ???jsp.display-item.citation.isi??? ND
social impact