This work addresses the energy performance of a solar DEC HVAC system working with the freescoo technology coupled with DHW tank for hot water preparation. Freescoo is a patented solar air conditioning concept for ventilation, cooling, dehumidification and heating of buildings for residential and tertiary sectors.The work presents monitoring results of a system installed at the ENEA Research Center in Lampedusa island. The monitoring of the system started in 2017 and here results for cooling operation are presented. Global seasonal electrical COP of about 10 have been registered.
Monitoring and Energy Performance Assessment of the Compact DEC HVAC System “Freescoo Facade” in Lampedusa (Italy)
Beccali, Marco;Motta, Mario;
2018-01-01
Abstract
This work addresses the energy performance of a solar DEC HVAC system working with the freescoo technology coupled with DHW tank for hot water preparation. Freescoo is a patented solar air conditioning concept for ventilation, cooling, dehumidification and heating of buildings for residential and tertiary sectors.The work presents monitoring results of a system installed at the ENEA Research Center in Lampedusa island. The monitoring of the system started in 2017 and here results for cooling operation are presented. Global seasonal electrical COP of about 10 have been registered.File in questo prodotto: