This paper evaluates the operation of an HVDC interconnection for providing virtual inertia and the impact on the power system frequency dynamics when one or both the converter terminals are controlled as a virtual synchronous machine (VSM). The analysis aims at assessing the performance of the inertia support from a power system perspective by studying the impact on the frequency nadir and the Rate-of Change-of-Frequency (RoCoF) of two asynchronous power system equivalents. It is demonstrated how the dc voltage control can be integrated with the VSM-based control when both converter terminals should be controlled to provide inertia support, but it is also found that this may require additional capacitance to ensure sufficient stability margins. Simulations in PowerFactory are presented for a case with two asynchronous power system equivalents connected by an HVDC transmission scheme modelled with parameters based on the planned Nordlink connection between Norway and Germany. The results confirm the beneficial effects of the inertia support on the frequency dynamics and demonstrate how the VSM-based control provides a clear improvement of the frequency nadir compared to traditional power-frequency droop control.

Impact on power system frequency dynamics from an HVDC transmission system with converter stations controlled as virtual synchronous machines

Palombi F.;Piegari L.;
2019-01-01

Abstract

This paper evaluates the operation of an HVDC interconnection for providing virtual inertia and the impact on the power system frequency dynamics when one or both the converter terminals are controlled as a virtual synchronous machine (VSM). The analysis aims at assessing the performance of the inertia support from a power system perspective by studying the impact on the frequency nadir and the Rate-of Change-of-Frequency (RoCoF) of two asynchronous power system equivalents. It is demonstrated how the dc voltage control can be integrated with the VSM-based control when both converter terminals should be controlled to provide inertia support, but it is also found that this may require additional capacitance to ensure sufficient stability margins. Simulations in PowerFactory are presented for a case with two asynchronous power system equivalents connected by an HVDC transmission scheme modelled with parameters based on the planned Nordlink connection between Norway and Germany. The results confirm the beneficial effects of the inertia support on the frequency dynamics and demonstrate how the VSM-based control provides a clear improvement of the frequency nadir compared to traditional power-frequency droop control.
2019
2019 IEEE Milan PowerTech, PowerTech 2019
978-1-5386-4722-6
Frequency dynamics; HVDC transmission systems; Virtual inertia; Virtual synchronous machines; elettrici
File in questo prodotto:
File Dimensione Formato  
powertech2019.pdf

Accesso riservato

Descrizione: paper
: Publisher’s version
Dimensione 230.53 kB
Formato Adobe PDF
230.53 kB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1121349
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 9
  • ???jsp.display-item.citation.isi??? 9
social impact