An experimental comparison of the use of R134a and R1234ze(E) in a semi-hermetic reciprocating compressor is presented in this paper. The comparison deals with the mass flow rate at compressor suction, the compressor power consumption and refrigerant temperature at compressor discharge. These parameters are measured using a dedicated experimental set-up. Twenty-five experimental working conditions that cover a large part of the compressor envelope are considered and a fitting procedure as per international standards is carried out for a deeper comparison. The results show that the use of the refrigerant R1234ze(E) leads to an average reduction of the sucked mass flow rate equal to 19.4%, to an average reduction of the compressor power consumption equal to 24.4% and to an average reduction of refrigerant temperature at compressor discharge equal to 9.2 °C.

Experimental comparison of the use of R134a and R1234ze(E) in a semi-hermetic reciprocating compressor

Luca MOLINAROLI;Andrea LUCCHINI;Luigi Pietro Maria COLOMBO
2019-01-01

Abstract

An experimental comparison of the use of R134a and R1234ze(E) in a semi-hermetic reciprocating compressor is presented in this paper. The comparison deals with the mass flow rate at compressor suction, the compressor power consumption and refrigerant temperature at compressor discharge. These parameters are measured using a dedicated experimental set-up. Twenty-five experimental working conditions that cover a large part of the compressor envelope are considered and a fitting procedure as per international standards is carried out for a deeper comparison. The results show that the use of the refrigerant R1234ze(E) leads to an average reduction of the sucked mass flow rate equal to 19.4%, to an average reduction of the compressor power consumption equal to 24.4% and to an average reduction of refrigerant temperature at compressor discharge equal to 9.2 °C.
2019
Proceedings of the 25th IIR International Congress of Refrigeration
978-2-36215-035-7
Compressor, Experimentation, R1234ze(E), R134a
File in questo prodotto:
File Dimensione Formato  
Experimental comparison of the use of R134a and R1234ze(E) in a semi-hermetic reciprocating compressor.pdf

Accesso riservato

Descrizione: Articolo principale
: Publisher’s version
Dimensione 546.25 kB
Formato Adobe PDF
546.25 kB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.