Critical facilities with high technological content like hospitals are characterized by a massive presence of earthquake-sensitive non-structural utilities and equipment whose full operation is essential in the aftermath of strong seismic events. The paper deals with several aspects of the design of seismically isolated medical centres with focus on their non-structural components. A simplified design procedure is exemplified using as case study the hospital of Lamezia Terme, located in a high seismic prone area in southern Italy, for which a seismic retrofit intervention with curved surface sliders is proposed. The preliminary sizing of the isolation system is guided by structural and non-structural targets. The protection of utilities and medical equipment requires indeed, at different seismic intensities, very stringent performance limitations, and specific thresholds are formulated to ensure both the structural integrity of the building at the ultimate states and the full operation at the service limit states. Nonlinear time-history analyses performed on the retrofitted building demonstrate the effectiveness of the procedure, by showing that, for the four design levels established by the Italian Building Code, the adopted solution provides the operation of the medical complex for frequent and occasional earthquakes and fulfils the immediate occupancy structural level for high intensity very rare earthquakes.

Seismic isolation retrofit of hospital buildings with focus on non-structural components

E. Gandelli;V. Quaglini;P. Dubini;M. P. Limongelli;S. Capolongo
2018-01-01

Abstract

Critical facilities with high technological content like hospitals are characterized by a massive presence of earthquake-sensitive non-structural utilities and equipment whose full operation is essential in the aftermath of strong seismic events. The paper deals with several aspects of the design of seismically isolated medical centres with focus on their non-structural components. A simplified design procedure is exemplified using as case study the hospital of Lamezia Terme, located in a high seismic prone area in southern Italy, for which a seismic retrofit intervention with curved surface sliders is proposed. The preliminary sizing of the isolation system is guided by structural and non-structural targets. The protection of utilities and medical equipment requires indeed, at different seismic intensities, very stringent performance limitations, and specific thresholds are formulated to ensure both the structural integrity of the building at the ultimate states and the full operation at the service limit states. Nonlinear time-history analyses performed on the retrofitted building demonstrate the effectiveness of the procedure, by showing that, for the four design levels established by the Italian Building Code, the adopted solution provides the operation of the medical complex for frequent and occasional earthquakes and fulfils the immediate occupancy structural level for high intensity very rare earthquakes.
2018
hospitals; seismic-retrofit; base isolation; Curved Surface Sliders; nonstructural components; performance-targets
File in questo prodotto:
File Dimensione Formato  
Ingegneria Sismica_2018.pdf

Accesso riservato

: Publisher’s version
Dimensione 1.69 MB
Formato Adobe PDF
1.69 MB Adobe PDF   Visualizza/Apri

I documenti in IRIS sono protetti da copyright e tutti i diritti sono riservati, salvo diversa indicazione.

Utilizza questo identificativo per citare o creare un link a questo documento: https://hdl.handle.net/11311/1072414
Citazioni
  • ???jsp.display-item.citation.pmc??? ND
  • Scopus 15
  • ???jsp.display-item.citation.isi??? 13
social impact